A.- THREE PHASEÂ RECLOSERÂ 33 KV | Â | Â | Â | |
ITEM | DESCRIPTION | UNIT | REQUIRED | GUARANTEED |
1 | RECLOSER | Â | Â | Â |
1.01 | COUNTRY | Â | TO INDICATE | Â Â CHINA |
1.02 | MANUFACTURER | Â | TO INDICATE | HEMG |
1.03 | MODEL | Â | TO INDICATE | CHZ4 |
1.04 | STANDARD | Â | ANSI C-37.60 | ANSI-37.60 |
1.05 | TYPE | Â | OUTDOOR | OUTDOOR |
1.06 | SYSTEM | Â | THREE PHASE | THREE PHASE |
1.07 | OPERATION TYPE | Â | AUTOMATIC AND MANUAL | AUTOMATIC AND MANUAL |
1.08 | ALTITUDE OF OPERATION | MO.S.L | 2500 OR MORE | 2500 OR MORE |
 | ELECTRIC CHARACTERISTICS |  |  |  |
1.09 | OPERATIONÂ VOLTAGE | KV | 33 | 33 |
1.10 | MAX, VOLTAGE OF THE EQUIPMENT | KV | 38 | 38 |
1.11 | NOMINALÂ FREQUENCY | HZ | 60 | 60 |
1.12 | NOMINAL CURRENT | A | 630 | 630 |
1.13 | NOMINAL SYMETRIC INTERRPTION CURRENT | KA | 12.5 | 12.5 |
1.14 | SPECIFICÂ LEAKAGEÂ DISTANCE | mm/KV | 31 | 31 |
1.15 | BIL | KV | 170 | 170 |
1.16 | DISCHARGE VOLTAGE, DRY, 60 HZ, 1 MINUTE | KV | 70 | 70 |
1.17 | DISCHARGE VOLTAGE, WET, 60 HZ, 10 SECONDS | KV | 60 | 60 |
1.18 | CYCLE OF WORK ACCORDÂ ANSI C-37.60 | Â | YES | YES |
1.19 | INTERRUPTIION WAY | Â | VACUUM | VACUUM |
1.20 | INSULATION WAY | Â | SOLID DIELECTRIC OR GAS SF6 | SOLID DIELECTRIC |
1.21 | NUMBER OF ELECTRIC OPERATIONS | Â | 10000 | 10000 |
1.22 | CURRENT MEASURE | Â | WITH CURRENT SENSORS | WITH CURRENT TRANSFORMER |
 | INSTALLATION |  | INDOOR | INDOOR |
 | SYSTEM |  | SINGLE PHASE | SINGLE PHASE |
1.23 | RELATION OF TRANSFORMATION | A | 400/1. | RELATION 1. |
1.24 | PRECISION | % | 1% | 1% |
1.25 | VOLTAGE MEASURE | Â | VOLTAGE SENSORS INTERNAL | VOLTAGE SENSORS INTERNAL |
1.26 | TYPE | Â | CAPACITIVE | CAPACITIVE |
1.27 | INSTALLATION | Â | IN BUSHING | IN BUSHING |
1.28 | PRECISION | % | 2.5 | 2.5 |
1.29 | QUANTITY | Â | 6 | 6 |
1.3 | SENSITIVE GROUND FAULT CURRENT DETECTION. | Â | CURENTÂ TRANSFORMER | SENSITIVE CURRENT TRANSFORMER |
 | INSTALLATION. |  | IN THE TANK (INSIDE THE TANK ) | IN THE CONTROL BOX |
 | QUANTITY. |  | 1 | 1 |
 | TRANSFORMATION RELATION. | Ma | 200/1.5 | (200/1.5) |
 | MECHANIC CHARACTERISTICS |  |  |  |
1.3 | METALLIC HARDWARE | Â | Â | Â |
 | MATERIAL |  | STAINLESS | STAINLESS |
 | STANDARD OF THE MATERIAL |  | ASTM A575 | ASTM A575 |
 | STANDARD OF HOT GALVANIZED |  | ASTM A 153 | ASTM A 153 |
 | THICKNEES OF GALAVANIZATION MIN | gr/CM2 | 800 | 800 |
1.31 | MOUNTING | Â | ON CIRCULAR POLE | ON CIRCULAR POLE |
1.32 | MECHANISM OF OPERATION | Â | MAGNETIC ACTUATOR | MAGNETIC ACTUATOR |
1.33 | POSITION INDICATOR | Â | VISIBLE FROM THE SOIL | VISIBLE FROM THE SOIL |
1.34 | OPERATION BETWEEN POLE WITHÂ HOOK | Â | YES | YES |
1.35 | MANUAL LOCKING EMERGENCY (ATTACHED DRAWING) | Â | YES | YES |
1.36 | TOOL PROVIDED WITH MANUAL CONTROL | Â | YES | YES |
1.37 | Â WITH LIFTING HOOKS | Â | YES | YES |
1.38 | INDICATES THE LIFE OF CONTACTS | Â | YES | YES |
1.39 | NUMBER OF MECHANICS OPERATION | Â | 10000 OR MORE | 10000 OR MORE |
1.40 | FULLYÂ ASSEMBLED | Â | YES | YES |
1.41 | WEIGHTÂ Â | Â | Â | Â |
 | PRINCIPAL TANK | KG | TO INDICATE | 135 |
 | CONTROL BOX | KG | TO INDICATE | 35 |
2 | TANK | Â | Â | Â |
2.01 | MATERIAL | Â | STAINLESS STEEL | STAINLESS STEEL |
 | CONSTRUCTION REQUIREMENTS |  | INDICATE THE STANDARD | INDICATE THE STANDARD |
2.02 | Â COATING OF TIN IN TERMINALS AND CONDUCTIVEÂ PARTS. | Â | 8 um | 8 um |
2.03 | PROTECTION DEGREE | Â | Able to withstand pressure fresh water cleaning insulators. | Able to withstand pressure fresh water cleaning insulators. |
3 | BUSHINGS | Â | Â | Â |
3.01 | COUNTRY | Â | TO INDICATE | CHINA |
3.02 | MANUFACTURER | Â | TO INDICATE | XINXIN |
3.03 | STANDARD | Â | ASTM D624, DIN 63504,IEC 60587,ASTM G154, AST G 155. | ASTM D624, DIN 63504,IEC 60587,ASTM G154, AST G 155. |
3.04 | CHARACTERISTICS OF MANUFACTURE | Â | Â | Â |
 | MATERIAL OF CORE |  | FIBER GLASS OR RESYN | RESYN |
 | INSULATION MATERIAL OF COVER HOUSING AND SHEDS |  | Cycloaliphatic EPOXY RESIN | Cycloaliphatic EPOXY RESIN |
 | ELONGATION AT BREAK | % | 450 ( ACCORD STANDARD DIN 53504 ) | 450 |
3.05 | TEAR RESISTANCE. | N/M | MAJOR OF 20 ( Standard ASTM D624) | 20 |
3.06 | TRACKING AND EROSION RESISTANCE. | Â | CLASS 2A,4.5 ( IEC 60587 ) | CLASS 2A,4.5 ( IEC 60587 ) |
3.07 | TESTING OF RESISTANCE TO UV RAYS. | Â | ACCORDING ASTM G154 AND ASTM G155 | ACCORDING ASTM G154 AND ASTM G155 |
3.08 | RANGE OF SECTION OF DRIVERS. | Â | 16Â TO 120 MM2 | 16Â TO 120 MM2 |
3.09 | CONDUCTOR MATERIAL OF ELIGIBLE. | Â | CU/AL , CU/CU , AL/AL | CU |
4 | SYSTEM OF CONTROL AND PROTECTION | Â | Â | Â |
4.01 | COUNTRY | Â | SAME COUNTRYÂ INDICATE POINT 1.1 | China |
4.02 | STANDARD OF MANUFACTURE | Â | ANSI / IE
LED outdoor lighting provides aesthetic
beauty and utility to architecture. It light building, pathways, walls, garden,
fountain, etc. almost anything outdoors you want to illuminate. Our high
quality fixtures come in variety of finishes, sizes and styles to reflect
project requirement. Led Outdoor Light,Led Flood Light,Led High Bay Light,Led Street Light ZHONGSHAN G-LIGHTS LIGHTING CO., LTD. , http://www.glightsled.com |
38kv Pole Mounted Recloser with 6PCS Voltage Sensror with 3 PCS CT in Bushing
Model NO.: CHZ4
Certification: ISO9001-2000
Trademark: HEMG
Transport Package: Carton with Wooden
Specification: 15KV/27KV/38KV, 50HZ/60HZ,
Origin: China
Model NO.: CHZ4
Certification: ISO9001-2000
Trademark: HEMG
Transport Package: Carton with Wooden
Specification: 15KV/27KV/38KV, 50HZ/60HZ,
Origin: China
Â